NX600 4x6 mm2
NX600 4x6 mm2
0,6/1 kV multi core low smoke halogen free, flame and fire resistant cables
Read more- Nexans ref. : 10539731
- Country ref. : TR
- EAN : 8680969090681
Description
Description
Standards
-
ProductBS 7846; BS 8519 cat. 3
-
TestBS 6387 CWZ
Application
- Indoor applications where fire safety is a priority (hotels, schools, high-rise buildings, hospitals, data centers, airports, offices etc.)
- Systems that require 180 minutes of circuit integrity during fire conditions:
- Warning Systems (fire alarms, smoke detection/alarm devices)
- Smoke Ventilation Systems (tunnel fans)
- Emergency Exits (emergency lighting fixtures)
- Fire Intervention Systems (water pumps, automatic doors)
- Uninterruptible Energy Systems (escalators, elevators in subways)
Construction
- Conductor: Copper
- Fire barrier: Mica tape
- Insulation: XLPE
- Inner layer: Glass-fiber tape
- Bedding: LSZH
- Armour: Single layer of galvanized steel wires
- Outer layer: Glass-fiber tape
- Outer sheath: LSZH
Characteristics
Characteristics
Construction characteristics
Construction characteristics
Conductor material
Copper
Armour type
Single layer of galvanized steel wires
Outer sheath
LSZH
Insulation
XLPE + Mica tape
Sheath colour
Black
Conductor flexibility
Class 2
Conductor shape
Circular stranded (RM)
Core identification
Blue, brown, black, grey
Halogen free
Yes
Inner sheath
None
Type of conductor
Circular, stranded, class 2
Dimensional characteristics
Dimensional characteristics
Number of cores
4
Approximate weight
1060 kg/km
Average insulation thickness
- mm
Conductor cross-section
6 mm²
Conductor diameter
- mm
Inner sheath thickness
- mm
Nominal outer diameter
24.0 mm
Nominal outer sheath thickness
- mm
Electrical characteristics
Electrical characteristics
Rated Voltage Uo/U (Um)
0,6/1 kV
Max. DC resistance of the conductor at 20°C
3.08 Ohm/km
Permissible current rating clipped direct
53 A
Permissible current rating in open air
56 A
Permissible current rating when buried
44 A
Permissible short circuit current conductor 1s
0.9 kA
Voltage Drop
6.8 V/A.km
Mechanical characteristics
Mechanical characteristics
Mechanical resistance to impacts
Good
Usage characteristics
Usage characteristics
操作温度范围
-20 ... 60 °C
Max. conductor temperature in service
90 °C
Fire resistant
BS 8491 - 120 min
Smoke density
IEC 61034-1-2
Gases corrosivity
IEC 60754-2
Flame retardant
IEC 60332-3-24
Bending factor when laying
8 (xD)
Short-circuit max. conductor temperature
250 °C
Resources
Resources
Selling & delivery Information
Marking
ELECTRIC CABLE 600/1000 V BS 7846-F120 NEXANS i NX600 Number of cores x cross section LPCB 946d/01 BASEC ''YEAR''