H07ZZ-F ALSECURE FLEX Dca

Products

H07ZZ-F 1X120 ALSECURE FLEX GL2000

Nexans ref. 10056852

  • Packaging: Cut to length (m)
  • Conductor cross-section: 120 mm²
  • Permissible current rating in open air: 382 A
  • Voltage drop, single phase: 0.36 V/A.km
  • Permissible mobile installation current: 270 A

 

H07ZZ-F 1X150 ALSECURE FLEX GL2000

Nexans ref. 10056660

  • Packaging: Cut to length (m)
  • Conductor cross-section: 150 mm²
  • Permissible current rating in open air: 441 A
  • Voltage drop, single phase: 0.31 V/A.km
  • Permissible mobile installation current: 312 A

 

H07ZZ-F 1X185 ALSECURE FLEX GL2000

Nexans ref. 10056441

  • Packaging: Cut to length (m)
  • Conductor cross-section: 185 mm²
  • Permissible current rating in open air: 506 A
  • Voltage drop, single phase: 0.28 V/A.km
  • Permissible mobile installation current: 358 A

 

H07ZZ-F 1X240 ALSECURE FLEX GL1000

Nexans ref. 10056442

  • Packaging: Cut to length (m)
  • Conductor cross-section: 240 mm²
  • Permissible current rating in open air: 599 A
  • Voltage drop, single phase: 0.23 V/A.km
  • Permissible mobile installation current: 424 A

 

H07ZZ-F 1X300 ALSECURE FLEX GL1000

Nexans ref. 10069724

  • Packaging: Cut to length (m)
  • Conductor cross-section: 300 mm²
  • Permissible current rating in open air: 693 A
  • Voltage drop, single phase: 0.2 V/A.km
  • Permissible mobile installation current: 490 A

 

H07ZZ-F 1X35 ALSECURE FLEX M/M GL4000

Nexans ref. 10171274

  • Packaging: Cut to length (m)
  • Conductor cross-section: 35 mm²
  • Permissible current rating in open air: 169 A
  • Voltage drop, single phase: 1.04 V/A.km
  • Permissible mobile installation current: 120 A

 

H07ZZ-F 1X400 ALSECURE FLEX GL1000

Nexans ref.

  • Packaging: Cut to length (m)
  • Conductor cross-section: 400 mm²
  • Permissible current rating in open air: 825 A
  • Voltage drop, single phase: 0.18 V/A.km
  • Permissible mobile installation current: 583 A

 

H07ZZ-F 1X50 ALSECURE FLEX GL4000

Nexans ref. 10063750

  • Packaging: Cut to length (m)
  • Conductor cross-section: 50 mm²
  • Permissible current rating in open air: 207 A
  • Voltage drop, single phase: 0.75 V/A.km
  • Permissible mobile installation current: 146 A

 

H07ZZ-F 1X50 ALSECURE FLEX GL4000

Nexans ref. 10286785

  • Packaging: Cut to length (m)
  • Conductor cross-section: 50 mm²
  • Permissible current rating in open air: 207 A
  • Voltage drop, single phase: 0.75 V/A.km
  • Permissible mobile installation current: 146 A

 

H07ZZ-F 1X500 ALSECURE FLEX GL1000

Nexans ref.

  • Packaging: Cut to length (m)
  • Conductor cross-section: 500 mm²
  • Permissible current rating in open air: 946 A
  • Voltage drop, single phase: 0.16 V/A.km
  • Permissible mobile installation current: 669 A

 

H07ZZ-F 1X630 ALSECURE FLEX GL500

Nexans ref. 10285245

  • Packaging: Cut to length (m)
  • Conductor cross-section: 630 mm²
  • Permissible current rating in open air: 1088 A
  • Voltage drop, single phase: 0.13 V/A.km
  • Permissible mobile installation current: 769 A

 

H07ZZ-F 1X70 ALSECURE FLEX GL3000

Nexans ref. 10063751

  • Packaging: Cut to length (m)
  • Conductor cross-section: 70 mm²
  • Permissible current rating in open air: 268 A
  • Voltage drop, single phase: 0.56 V/A.km
  • Permissible mobile installation current: 190 A

 

H07ZZ-F 1X95 ALSECURE FLEX GL3000

Nexans ref. 10056440

  • Packaging: Cut to length (m)
  • Conductor cross-section: 95 mm²
  • Permissible current rating in open air: 328 A
  • Voltage drop, single phase: 0.44 V/A.km
  • Permissible mobile installation current: 232 A

 

Description

Description

Standards

  • Product
    EN 50525-3-21; EN 50575; IEC 60228

Application

This cable is particularly recommended for all installations in which safety conditions require the use of a flexible and low smoke cable :

  • wiring for industrial installations,
  • wiring for road and rail tunnels,
  • wiring for industrial warehouses,
  • wiring for rooms containing electrical, electronic or computer equipment,
  • wiring for central control rooms,
  • wiring for airports stations, port facilities and ships
  • wiring for hospitals,
  • wiring for buildings open to the public,
  • wiring for house and tall buildings.

Nota

Max continuous operating conductor temperature in normal use :

+60°C   ( in every case of mobile installation)

+90°C   ( fixed protected installation )

+250°C ( in short circuit )

 

Permissible current rating is measured for an ambient temperature of 30°C and a
maximum operating and conductor temperature of 90°C according IEE 4F2A table. For
other temperature please refer to correction factors .

Characteristics

Characteristics

Construction characteristics

Construction characteristics

Conductor material
Bare copper
Outer sheath
Special cross-linked elastomer
Sheath colour
Black
Lead free
Yes
With Green/Yellow core
No
Conductor shape
Circular

Dimensional characteristics

Dimensional characteristics

Number of cores
1

Electrical characteristics

Electrical characteristics

Rated Voltage Uo/U (Um)
450/750 V

Mechanical characteristics

Mechanical characteristics

Mechanical resistance to impacts
Very good
Cable flexibility
Flexible

Usage characteristics

Usage characteristics

Packaging
Cut to length
Chemical resistance
Accidental
Water proof
Good
Max. conductor temperature in service
90 °C
Oil resistance
Yes
Short-circuit max. conductor temperature
250 °C
操作温度范围
-25 ... 55 °C

Resources

Resources

Documentation

License USE pdf — 613.8 kB

Contact us

Topics on which you wish to get more informations:

Required fields*

Please check your entry and try again.

An email address must contain a single @

Personal data protector

You have the right to object to the processing of your personal data and/or their use for direct marketing or commercial purposes

Thank you!

Thanks for contacting us. We will be in touch with you shortly.

Error

An error occurred. Please try again.

Close

Contact us

Required fields*

Please check your entry and try again.

An email address must contain a single @

Personal data protector

You have the right to object to the processing of your personal data and/or their use for direct marketing or commercial purposes

Thank you!

Thanks for contacting us. We will be in touch with you shortly.

Error

An error occurred. Please try again.

Close